Please use this identifier to cite or link to this item: http://hdl.handle.net/123456789/1752
Title: Ultrasonic disinfection of drinking water
Authors: Stefanescu, Mihai 
Ionescu, Ioana 
Affiliations: National Research and Development Institute for Industrial Ecology, ECOIND 
National Research and Development Institute for Industrial Ecology, ECOIND 
Keywords: Drinking water;Sonolysis;Aerobic mesophylls bacteria
Issue Date: 2017
Publisher: ARA Publishing
Abstract: 
Experimental tests were performed on surface water samples after coagulation-flocculation settling treatment steps. The main operating parameters of sonolysis experiments were as follows: ultrasound frequency 20 kHz (constant for all tests), sonolysis time 2 - 50 min., ultrasound energy 2000 - 8000 kJ, ultrasound amplitude 20 - 80%, hydrogen peroxide doses 2 - 10 mg H2O2/L.
Aerobic mesophiles bacteria (37 0C) content was measured and the best removal efficiency was 97% (initial content 9x104 CFU/ml) for direct sonolysis and over 99.9% for hybrid sonolysis in case of short irradiation time.
Description: 
International Conference “Sustainable Solutions in Water Management 2017”, ARA, 15-17.05.2017, Bucharest
URI: http://hdl.handle.net/123456789/1752
Appears in Collections:Conference Papers

Files in This Item:
File Description SizeFormat
Mihai Stefanescu full paper ARA conference 2017.pdfPresentation171.97 kBAdobe PDFView/Open